Concealed Space Sprinklers Case Study
You have asked the following questions: “The concealed space sprinklers per 8.15.1.6 indicates that concealed spaces less than 3 ft shall be protected using listed sprinklers. We have an open wood truss construction that is tapered with the above portion being 5 ft and the lower being 2 ft. Concealed space sprinklers have specific requirements one of which is they are not listed in spaces greater than 3 ft. Q1) Should truss spaces be protected by standard spray sprinklers throughout? Q2) Should the space be protected by concealed space sprinklers throughout? Q3): Should space be protected by a combination of standard spray and concealed space sprinklers? If so, which design strategy is applied (area/density or concealed space strategy)?” In response to your questions, we have reviewed NFPA 13, 2016 edition as the applicable standard. Our informal interpretation is that there are several approaches that can be used for this application.
The wording in the standard may not be the best, but this section is requiring the use of sprinklers listed for applications for horizontal combustible concealed spaces less than 36 in. deep. As noted in the Handbook commentary, listed standard spray sprinklers were ineffective for fire control since the shallow space inhibits the discharge pattern development. When the space is greater
…show more content…
The minimum size of the remote area for standard spray sprinklers in this space would be 900 sq. ft. If there is insufficient area, the remote area is carried to the concealed space sprinklers. The other calculation would be the concealed space sprinklers having a minimum remote area size of 1,000 sq. ft. There is no requirement to separate the two types of sprinklers. The exception is the draft curtains required by the manufacturer’s data sheets for the listed concealed space sprinklers. Refer to the sprinkler’s data sheets for the specifics on the draft

You May Also Find These Documents Helpful

  • Good Essays

    Nt1330 Unit 5

    • 800 Words
    • 4 Pages

    3.Windows in these walls must be non-operable fire windows (exceptions for bathroom toilet or laundry windows with an area smaller than 1.2m2…

    • 800 Words
    • 4 Pages
    Good Essays
  • Satisfactory Essays

    Over the past year these rare Mathemafish are being threaten by the Fluted Dropout Shark. As months pass the population is starting to decrease more and more. We are finding that out through the catch-tag-release method (method that allows us to track the fish) that the past twelve months the population which started at 480 has dropped to 46.…

    • 393 Words
    • 2 Pages
    Satisfactory Essays
  • Powerful Essays

    Nt1310 Unit 3 Assignment 3

    • 4996 Words
    • 20 Pages

    This document is copyrighted by the National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, MA 02269-9101 USA.…

    • 4996 Words
    • 20 Pages
    Powerful Essays
  • Good Essays

    Not more than three months after the November fire, Nevada’s building and fire codes were revised to have the most strict fire sprinkler and life safety codes in the country. All hotels larger than fifty-five feet in height were required to be retrofitted with fire sprinkler systems. Also, all future building constructed of three or more stories were required to install fire…

    • 809 Words
    • 4 Pages
    Good Essays
  • Better Essays

    References: DuPont. (2013, n.d n.d). DuPont™ FM-200® Waterless Fire Suppression Systems. Retrieved November 29, 2013, from A Dupont Website: http://www2.dupont.com/FE/en_US/products/FM200.html#.UpmIz8RDt8E…

    • 1902 Words
    • 8 Pages
    Better Essays
  • Satisfactory Essays

    If the trench is 20 feet or greater the protective system needs to be designed by a registered professional engineer or be based on tabulated data prepared and/or approved by a registered professional engineer according to 1926.652(b) and (c).…

    • 360 Words
    • 2 Pages
    Satisfactory Essays
  • Better Essays

    Qcf 643

    • 1083 Words
    • 5 Pages

    | Describe how and when the different types of fire extinguishers, relevant to the given occupation, are used in accordance with legislation and official guidance.…

    • 1083 Words
    • 5 Pages
    Better Essays
  • Good Essays

    Football Field Problems

    • 445 Words
    • 2 Pages

    Problem three consists of a football field that needs a new irrigation system. The best route for the water pipes, location of the sprinklers, what part of the field each sprinkler waters, and how much of the field each sprinkler waters had to be determined. While figuring this out, the whole football field has to be watered without being over watered. The sprinkler placed in the corners will cover ¼ of a circle and it will spray at a 90 degree angle.…

    • 445 Words
    • 2 Pages
    Good Essays
  • Good Essays

    User Manual Critique

    • 923 Words
    • 3 Pages

    Turf Sprayer. The website address for this manual is: https://icontent.toro.com/smartmanuals/MultiPro_1250/Proc12891.htm. I used the following criteria to critique this manual, audience recognition, components of instructions, safety instructions, instructional steps and finally graphics and videos.…

    • 923 Words
    • 3 Pages
    Good Essays
  • Satisfactory Essays

    As mentioned above, the idea behind this tactic is to get water onto the fire as soon as possible. If this can be achieved, the fire will remain cooler and more controlled for a limited amount of time allowing for fire crews to quickly search for victims (search and rescue), locate power/utility shut off valves, and to get a better understanding of the structure’s lay out.…

    • 512 Words
    • 2 Pages
    Satisfactory Essays
  • Good Essays

    Colton Copy

    • 420 Words
    • 2 Pages

    a. What is the approximate size of the evacuation area? This area is about 30Km and is…

    • 420 Words
    • 2 Pages
    Good Essays
  • Good Essays

    Econ 201 N23-1

    • 1194 Words
    • 5 Pages

    AlwaysRain Irrigation, Inc., would like to determine capacity requirements for the next four years. Currently two production lines are in place for making bronze and plastic sprinklers. Three types of sprinklers are available in both bronze and plastic: 90-degree nozzle sprinklers, 180-degree nozzle sprinklers, and 360-degree nozzle sprinklers. Management has forecast demand for the next four years as follows:…

    • 1194 Words
    • 5 Pages
    Good Essays
  • Better Essays

    An emergency occurs when a urgent situation takes place that can be detrimental to a person’s life. Emergencies are not a common occurrence; however do arise on occasion. The response and outcome of emergencies can be positively amplified with an organized plan or preparedness technique. In “The Neighborhood” community, there was an emergency, forest fires, which left the residents to experience unfortunate residual respiratory effects. The many that suffered include patients and staff in the hospital, senior center, school, and the Bley household.…

    • 1447 Words
    • 6 Pages
    Better Essays
  • Good Essays

    Glass Pool Fencing Essay

    • 2018 Words
    • 9 Pages

    - The fence must be at least 1.2m high and no more than 100mm ground clearance.…

    • 2018 Words
    • 9 Pages
    Good Essays
  • Powerful Essays

    facilities. Each weapon reduces a specific amount of the covering radius. The interdictor’s objective is…

    • 1151 Words
    • 5 Pages
    Powerful Essays