The wording in the standard may not be the best, but this section is requiring the use of sprinklers listed for applications for horizontal combustible concealed spaces less than 36 in. deep. As noted in the Handbook commentary, listed standard spray sprinklers were ineffective for fire control since the shallow space inhibits the discharge pattern development. When the space is greater …show more content…
The minimum size of the remote area for standard spray sprinklers in this space would be 900 sq. ft. If there is insufficient area, the remote area is carried to the concealed space sprinklers. The other calculation would be the concealed space sprinklers having a minimum remote area size of 1,000 sq. ft. There is no requirement to separate the two types of sprinklers. The exception is the draft curtains required by the manufacturer’s data sheets for the listed concealed space sprinklers. Refer to the sprinkler’s data sheets for the specifics on the draft