Preview

Units for Refrigerant-Based Systems

Good Essays
Open Document
Open Document
529 Words
Grammar
Grammar
Plagiarism
Plagiarism
Writing
Writing
Score
Score
Units for Refrigerant-Based Systems
The chiller efficiency depends on the energy consumed. Absorption chillers are rated in fuel consumption per ton cooling. Electric motor driven chillers are rated in kilowatts per ton cooling. • KW/ton = 12 / EER • KW/ton = 12 / (COP x 3.412) • COP = EER / 3.412 • COP = 12 / (KW/ton) / 3.412 • EER = 12 / KW/ton • EER = COP x 3.412
If a chillers efficiency is rated at 1 KW/ton, • COP = 3.5 • EER = 12

Cooling Load in - kW/ton

The term kW/ton is commonly used for larger commercial and industrial air-conditioning, heat pump and refrigeration systems.
The term is defined as the ratio of energy consumption in kW to the rate of heat removal in tons at the rated condition. The lower the kW/ton the more efficient the system.
KW/ton = Pc / Er (1)
Where Pc = energy consumption (kW)
Er = heat removed (ton)

Coefficient of Performance - COP

The Coefficient of Performance - COP - is the basic parameter used to report efficiency of refrigerant based systems.
The Coefficient of Performance - COP - is the ratio between useful energy acquired and energy applied and can be expressed as
COP = Eu / Ea (2)
Where COP = coefficient of performance
Eu = useful energy acquired (btu in imperial units)
Ea = energy applied (btu in imperial units)
COP can be used to define either cooling efficiencies or heating efficiencies as for heat pumps. • Cooling - COP is defined as the ratio of heat removal to energy input to the compressor • Heating - COP is defined as the ratio of heat delivered to energy input to the compressor
COP can be used to define the efficiency at single standard or non-standard rated conditions, or as a weighted average of seasonal conditions. The term may or may not include the energy consumption of auxiliary systems such as indoor or outdoor fans, chilled water pumps, or cooling tower systems. • higher COP - more efficient system
COP can be treated as an efficiency where COP of

You May Also Find These Documents Helpful

  • Good Essays

    Mae219 Unit 9 Study Guide

    • 613 Words
    • 3 Pages

    A refrigerator operates on the ideal vapor compression refrigeration cycle with R-134a as the working fluid between the pressure limits of…

    • 613 Words
    • 3 Pages
    Good Essays
  • Good Essays

    Hvac

    • 673 Words
    • 3 Pages

    Shell and tube water cooled condensers Vertical shell and tube condensers Surface condenser Counter flow in condensers Cross flow in condensers Air cooled condensers Cooling Tower…

    • 673 Words
    • 3 Pages
    Good Essays
  • Powerful Essays

    The efficiency of a heat pump can be represented by the Coefficient of Performance (COP).…

    • 1241 Words
    • 5 Pages
    Powerful Essays
  • Good Essays

    Direct exchange systems are significantly more efficient and have potentially lower installation costs than closed loop water systems. Copper's high thermal conductivity contributes to the higher efficiency of the system, but heat flow is predominantly limited by the thermal conductivity of the ground, not the pipe. The main reasons for the higher efficiency are the elimination of the water pump (which uses electricity), the elimination of the water heat exchanger (which is a source of heat losses), and most importantly, the latent heat phase change of the refrigerant in the ground itself.…

    • 386 Words
    • 2 Pages
    Good Essays
  • Better Essays

    1. The New England colonies were characterized by greater social stability than both the southern and middle colonies. They were different mainly because of their geography. Unlike the New England colonies, the southern and middle colonies were far apart and had created their own individualistic societies when they settled, because they were so spread out. The New England colonies were very close together due to their mountainous geography so it was easy for them to maintain contact and have an organized government.…

    • 1418 Words
    • 6 Pages
    Better Essays
  • Satisfactory Essays

    Mr Khan

    • 379 Words
    • 2 Pages

    HES 2330 Thermodynamics 1 Semester 1 – 2013 ASSIGNMENT 2 Due Date: 29 May 2013, 5.00 PM Dropbox: Mailbox 83 (HES2330/HES4330) – Level 8, ATC Building 1. A container filled with 45 kg of liquid water at 95oC is placed in a 90-m3 room that is initially at 12oC. The thermal equilibrium is established after a while as a result of heat transfer between the water and the air in the room. Using constant specific heats, determine (a) the final equilibrium temperature, (b) the amount of heat transfer between the water and the air in the room, and (c) the entropy generation. Assume the room is well sealed and heavily insulated. 2. An ideal Otto cycle has a compression ratio of 9.2 and uses air as the working fluid. At the beginning of the compression process, air is at 98 kPa and 27oC. The pressure is doubled during the constant-volume heat-addition process. Accounting for the variation of specific heats with temperature, determine (a) the amount of heat transferred to the air, (b) the net work output, (c) the thermal efficiency, and (d) the mean effective pressure for the cycle. 3. A gas turbine power plant uses solar energy as the source of heat addition (see Figure for detailed setup and operating data). Modelling the cycle as a Brayton cycle and assuming no pressure drops in the heat exchanger or interconnecting piping, determine: (a) the thermal efficiency; (b) the air mass flow rate, in kg/s, for a net power output of 500kW.…

    • 379 Words
    • 2 Pages
    Satisfactory Essays
  • Good Essays

    Construction

    • 1502 Words
    • 7 Pages

    Governments and industry groups are preparing for enhanced energy efficiency. Some matters are currently required by the Building Code of Australia (BCA 5 star, BASIX for NSW) & others are becoming so. (eg. NABERS Energy) Along with these mandatory regulations voluntary schemes are also available. (Green Star, GreenPower). Below I will discuss these mandatory legislative & planning requirements as well as optional solutions for thermal efficiency.…

    • 1502 Words
    • 7 Pages
    Good Essays
  • Good Essays

    Thermos lab

    • 2047 Words
    • 9 Pages

    OBJECTIVE—of this exercise is to determine the various coefficients of performance, COP. Specifically, these are the ideal and actual cycle COPs using the attached thermodynamic diagram for Refrigerant-12 (R12).…

    • 2047 Words
    • 9 Pages
    Good Essays
  • Good Essays

    Title Title Titile

    • 273 Words
    • 2 Pages

    - a heat engine takes heat from a high temperature reservoir, converts some to useful work and rejects the remainder to the low temp reservoir.…

    • 273 Words
    • 2 Pages
    Good Essays
  • Better Essays

    individual assignment

    • 3335 Words
    • 14 Pages

    cooling device for this experiment with efficiency of 0.86 %. Qulatitive analysis was done with consideration of…

    • 3335 Words
    • 14 Pages
    Better Essays
  • Powerful Essays

    Data Center

    • 1238 Words
    • 11 Pages

    Begin with an efficient water cooled variable speed chiller, add high efficiency air handlers, low-pressure drop components, and finish with an integrated control system that minimizes unnecessary dehumidification and simultaneous heating and cooling. • Benchmark existing facilities Use temperature resets to allow use of medium-temperature chilled water (55 degrees Fahrenheit or higher). Warmer chilled water improves chiller plant efficiency and eliminates the need for the chiller during many hours of operation (tower cooling). • Continuously monitor energy and environmental conditions • Document design intent…

    • 1238 Words
    • 11 Pages
    Powerful Essays
  • Satisfactory Essays

    |Kilowatts x the Amount of Hours = kWh |Kilowatts x the Amount of Hours = kWh |…

    • 427 Words
    • 2 Pages
    Satisfactory Essays
  • Satisfactory Essays

    Essay on Frigoglass

    • 373 Words
    • 2 Pages

    2. Domestic cooling appliances like fridge and freezers…. the technology for the production is quite similar.…

    • 373 Words
    • 2 Pages
    Satisfactory Essays
  • Powerful Essays

    Accaounting

    • 656 Words
    • 3 Pages

    3) Overhead rate computed in Q 1 is higher than the rates computed in Q2. The rate computed in Q1 is based on the estimate of FFB harvested in both peak and low seasons whereby in Q2, the rate is based on the estimate of the annual FFB harvested.…

    • 656 Words
    • 3 Pages
    Powerful Essays
  • Powerful Essays

    Solar Ray Collector

    • 1168 Words
    • 5 Pages

    Solar ray collectors transform solar radiation into heat and transfer that heat to water. Then solar heat can be used for heating water, to back up heating systems. The heart of a solar collector is the absorber, which is usually composed of several narrow metal strips. The carrier fluid for heat transfer flows through a heat-carrying pipe, which is connected to the absorber strip. In plate-type absorbers, two sheets are sandwiched together allowing the medium to flow between the two sheets. Absorbers are typically made of copper or aluminum.…

    • 1168 Words
    • 5 Pages
    Powerful Essays

Related Topics