Preview

Vfd's on a Utility Cooling Tower

Good Essays
Open Document
Open Document
2538 Words
Grammar
Grammar
Plagiarism
Plagiarism
Writing
Writing
Score
Score
Vfd's on a Utility Cooling Tower
Petersburg Cooling Tower Auxiliary Power Usage with VFD’s/ Control Strategy
Michael J Smith – IPL Engineering & Project Management
Abstract--The temperature control strategy for the cooling tower fans involves two automatic modes of operation as well as provisions for manual operation. Both modes will provide sequencing for starting/stopping each of the 14-250hp, 480vac fans that have been made available for automatic control. Auxiliary power savings on the 3MVA, 4160vac tower load can be between 0.5 – 1.0MVA 6 months a year in the Midwest with the variable frequency drives (VFD’s). The first, automatic mode, HEAT RATE, will be aimed at operating the fans at or near the circulating water temperature which results in the optimal unit heat rate for the given load. The goal of the second mode, AUX POWER, will be to minimize the auxiliary power consumption by operating at or near the highest back pressure possible without reaching 7.0 inHgA. This mode is only intended for use during normal operation at full/ partial load, and not during start-up/shutdown. During both modes, the minimum circulating water temperature will not be allowed to go below 70o F at low ambient temperatures to prevent tower cell icing. Each fan may be operated manually in either bypass or through the VFD via the DCS or locally at the MCC. When all fans in AUTO have been running continuously at 1 00% speed for 15 minutes in either automatic control mode, a sequential transfer to BYPASS shall begin using fan hysteresis. In HEAT RATE mode, if none of the fans in AUTO are running, the first fan in the sequence shall be started and held at 25% minimum speed. The remaining available fans shall be sequentially started until all are at 25%. The speed set point shall then be raised to 100% for all fans. When AUX POWER mode is selected, the DCS PID will receive HP hot well temperature as its input. The set point shall be the saturation temperature corresponding to 6.25 in HgA (3.07 psi), with



References: Technical Papers: D. Oldham, Black and Veatch (May 4, 2005), “Cooling Tower Performance Specification Recommendations” Black and Veatch (October 14, 2005), “Indianapolis Power and Light- Petersburg Unit 3- Cooling Tower- Programmable Logic Controller- 140863.64.3600- General Specifications” Black and Veatch (March 10, 2006), “IPL Petersburg Unit 3- Cooling Tower Fan Analog Control- BV Project 140863” C. Barron, M. Wildeman, B. Horstman, Project Associates Inc. (December 20, 2010), “IPL Petersburg Generating Station- System Description Document- Unit 4 Cooling Tower Control” Cooling Tower Test Associates, Inc (March 21, 2012), “Summary of Test Results- Indianapolis Power & Light- Unit 4 in Petersburg, IN- Thermal Acceptance Test on the SPX Cooling Technologies 13 Cell, Mechanical Draft, Cross-Flow Cooling Tower” Michael J. Smith IPL (May 31, 2013) “U4 Cooling Tower Economic Analysis” Microsoft Excel 2010 Financial Spreadsheet Functions Author, Bios and photos Michael J. Smith is the Unit Manager, Engineering and Project Management for the Power Supply Division of Indianapolis Power & Light Co, Inc. He holds a BSEE from the University of Evansville in Evansville, IN, is certified as a Six Sigma Black Belt, and is currently pursuing an MBA to be completed November 2013. Smith formerly worked in automation consulting, heavy industry, and manufacturing with Amax, ALCOA, Whirlpool, and Hershey before joining the power industry in 2005.

You May Also Find These Documents Helpful

  • Powerful Essays

    Unit 4222-371

    • 20924 Words
    • 84 Pages

    Sealed Primary System ............................................Page 18 Open Vent Primary System .....................................Page 19 Domestic Hot Water .................................................Page 20 Electrical ....................................................................Page 21 Functional Flow Charts ............................................Page 24 Installation ................................................................Page 27 Commissioning…

    • 20924 Words
    • 84 Pages
    Powerful Essays
  • Powerful Essays

    assessment 1

    • 1591 Words
    • 7 Pages

    We have expertise in all facets of pressure vessel design and fabrication, specialising in cryogenic applications for products including Oxygen, Nitrogen, Argon, Carbon Dioxide, LNG (Liquefied Natural Gas), and Ethylene. We Have the Pleasure of Providing Products and Services to Some of the Worlds Larger Companies Ach as B.O.C. (MEMBER OF LINDE GROUP) , COREGAS , SUPAGAS (100% AUSTRALIAN) , AND HALLIBURTON.…

    • 1591 Words
    • 7 Pages
    Powerful Essays
  • Powerful Essays

    This paper discusses the proposal package for Riordan, which handles each step of electric fans from inception to production. The paper also includes the material requirement-planning phase of fans being manufactured at the China Plant. An analysis of the existing production process of the Riordan electric fans provides the basic outline for designing the new process to remove bottlenecks. In addition, the production…

    • 1778 Words
    • 8 Pages
    Powerful Essays
  • Good Essays

    The arena will be the first in the world to combine the use of displacement ventilation – a reduced-energy cooling system utilizing passive climate controlled air – and crowdsourced feedback to maximize fan comfort. Five massive hangar doors above the grand entrance will open and allow the arena to use natural cooling phenomenon in Sacramento – The Delta Breeze – to control the building’s climate efficiently. With over 300 days of sunshine in Sacramento, the arena’s urban-smart energy system – with a specially designed 1.2 megawatt solar array on the arena roof and an 11-megawatt solar farm 40 miles away through a SMUD partnership – provides a creative solution for generating the power for the venue’s over 200 events all year long (Golden one center,…

    • 1067 Words
    • 5 Pages
    Good Essays
  • Satisfactory Essays

    JBT Aerotech Memo

    • 377 Words
    • 2 Pages

    a. New competitive bid was issued by the U.S Air force for cooling units for aircrafts which will be used by the new F-35 platform.…

    • 377 Words
    • 2 Pages
    Satisfactory Essays
  • Good Essays

    Aldham Robarts Case Study

    • 960 Words
    • 4 Pages

    The resource centre has variable –volume refrigerant system used to provide cooling to the building.…

    • 960 Words
    • 4 Pages
    Good Essays
  • Better Essays

    Poorly written email

    • 1026 Words
    • 5 Pages

    I have had a chance to review your memorandum in detail, research the relevant codes and standards, and have some preliminary conversations with Matt Hirsch (Primus) and Mike McGinnis (Innovative). I have also attached two (2) pictures of the installation in Omaha. The installation in Dallas, although appears to be vessel, is not intended to be a vessel. The design that was reviewed initially was to be condenser drain header sized to provide a minimum of 5 minutes of liquid supply to the thermosyphon oil coolers. However, pipe cap fitting were used on the inlet and outlet sides of the header in Dallas in lieu of reducing fittings that were utilized in Omaha. I agree it looks like a vessel. We can debate definitions until we are blue in the face. Your memorandum to me is kind of all over the place and I struggle with what your real concern(s) is/are. I want to resolve this issue and any underlying issues that you might have.…

    • 1026 Words
    • 5 Pages
    Better Essays
  • Powerful Essays

    Feedback Control Dynamic System

    • 58216 Words
    • 233 Pages

    Notice that in a number of cases the same physical device may perform more than one of these functions.…

    • 58216 Words
    • 233 Pages
    Powerful Essays
  • Good Essays

    Ops/571 Week 6

    • 1445 Words
    • 5 Pages

    Riordion Manufacturing looks forward to hearing any opinions and concerns regarding the new development for processing of distributing the electric fans.…

    • 1445 Words
    • 5 Pages
    Good Essays
  • Powerful Essays

    Chillers

    • 2504 Words
    • 11 Pages

    A chiller is a machine that removes heat from a liquid via a vapor-compression or absorption refrigeration cycle. A vapor-compression water chiller comprises the 4 major components of the vapor-compression refrigeration cycle (compressor, evaporator, condenser, and some form of metering device). These machines can implement a variety of refrigerants. Adsorption chillers use municipal water as the refrigerant and benign silica gel as the desiccant. Absorption chillers utilize water as the refrigerant and rely on the strong affinity between the water and a lithium bromide solution to achieve a refrigeration effect. Most often, pure water is chilled, but this water may also contain a percentage of glycol and/or corrosion inhibitors; other fluids such as thin oils can be chilled as well.…

    • 2504 Words
    • 11 Pages
    Powerful Essays
  • Satisfactory Essays

    Build Your Own Computer

    • 415 Words
    • 2 Pages

    Intel BXRTS2011LC High Performance Liquid Cooler - 120mm Fan, 2200 RPM Max, 74 CMF, 35dBA Max, 150mm Radiator, LGA2011, LGA1155 $99.99…

    • 415 Words
    • 2 Pages
    Satisfactory Essays
  • Best Essays

    This report is intended for use by Business Development directors of Supermarkets with an international presence. It collects and interprets information pertaining to potential investment in Trigeneration technology. This includes; a review of the driving forces behind the developing trend towards renewable energy and sustainable energy technologies; what is required for the operation of the technology, the potential for return on investment.…

    • 4129 Words
    • 17 Pages
    Best Essays
  • Powerful Essays

    Industrial Ventilation

    • 5825 Words
    • 24 Pages

    This course is adapted from the Unified Facilities Criteria of the United States government, which is in the public domain, has unlimited distribution and is not copyrighted.…

    • 5825 Words
    • 24 Pages
    Powerful Essays
  • Powerful Essays

    Green Mark

    • 1158 Words
    • 5 Pages

    The main strategies are that we achieve an ETTV (Envelope Thermal Transfer Value) of 40/m^2 or lower, design system efficiency of 0.65 for the cooling system, 5.0 or more meters for the parameter of daylight zones from façade perimeters and installing solar panels on the roof to provide a renewable energy source.…

    • 1158 Words
    • 5 Pages
    Powerful Essays
  • Powerful Essays

    The Goal of this study/simulation is to find out the relation between the Building Glass type and the total amount of the cooling load needed to keep the building temperature within the comfort zone range. The Simulation focuses on the following three questions:…

    • 1763 Words
    • 8 Pages
    Powerful Essays