Faults and Transients on Transmission Lines
Wang Wei weiwan@kth.se 1/12/2011
1. Introduction
Project 1 is about fault currents and transients on transmission lines that may occur due a lightning strike to an overhead line. In this case the transmission line is energized from one side and it’s other side is terminated in a Gas Insulated Substation, see Fig. 1. Several issues will be investigated from this system such as transient overvoltages and short-circuit currents.
Fig.1 Transmission line model
1.1 Given parameters
System voltage Table 1. Basic power line data 420 kV 20 m 13 m 25 cm 25 mm 3800 Ohmm 0.5 m 0.5 m Do = 400 mm, Di = 120 mm
Average height above ground Phase-to-phase distance Triplex conductor, circumscribing diameter Conductor diameter Soil resistivity Tower grounded with metallic hemisphere of radius Generation station neutral grounded with metallic hemisphere of radius Co-axial GIS tube filled with SF6. Outer andd inner diameter
1
2.1 Stationary LLG fault current
A phase-to-phase to ground (LLG) fault occurs in the middle of the line, i.e. YY/2 km from each sub-station. OHL parameters The theory developed by Carson give the approximate expression for the distance to return conductor as a function of the resistivity of the earth and the frequency
D 658
f 658
3800 5736.31m 50
The geometric mean radius is given by
GMR 3 3 0.025 / 2 0.25 / 2 0.0837m
2
1 D 1 5736.31 L11 L22 L33 2 107 ( ln ) 2 107 ( ln ) 2.277 106 H / m 4 GMR 4 0.0837
Z11 Z22 Z33 j 2 fL11 l j 29.69
L12 L21 L23 L32 2 107 ln D 5736.31 2 107 ln 1.218 106 H / m d12 13
Z12 Z21 Z23 Z32 j 2 fL12 l j15.88
L13 L31 2 107 ln D 5736.31 2 107 ln 1.08 106 H / m d13 26
Z13 Z31 j 2 fL13 l j14.08
The impedance matrix can be obtained
j 29.69 Z j15.88 j14.08
j15.88 j 29.69 j15.88
j14.08 j15.88 j 29.69